Migrating from PROFIBUS to PROFINET: When Is It Worth Making the Switch?

The plant has been running for fifteen years—maybe longer—and PROFIBUS DP has rarely caused any problems during that time. Nevertheless, the same question now comes up regularly in many production and maintenance meetings: Should we switch to PROFINET? And if so, when?

Anyone who modifies a functioning system unnecessarily is investing in downtime and risk. Those who wait too long will eventually be left with a defective component that is nearly impossible to obtain. The decision lies between these two extremes, and it depends on a few, easily verifiable criteria: the condition of the control system, the planned changes to the system, and the requirements for diagnostics and data connectivity.

A Direct Comparison of PROFIBUS and PROFINET

PROFIBUS DP is a serial fieldbus. The devices are connected to a common two-wire line in a bus topology, the maximum transmission rate is 12 Mbit/s, and up to 126 addresses are possible per network. For the cyclic transmission of input and output data, this remains entirely sufficient in many systems to this day.

PROFINET IO, on the other hand, is based on Industrial Ethernet. Data is transmitted at 100 Mbit/s in full-duplex mode, the topology can be freely selected, and the number of participants is limited practically only by the controller. In operation, however, another factor is even more important: In addition to process data, PROFINET also handles diagnostics, parameterization, and IT communication over the same network.

PROFIBUS DP PROFINET IO
Transmission Technology RS-485, two-wire line Industrial Ethernet
Data rate up to 12 Mbit/s 100 Mbit/s full-duplex
Topology Line Line, star, tree, ring
Users Up to 126 addresses per network Practically limited by the controller
Diagnostics Limited, often requiring additional tools Integrated down to the port level
Device description GSD file GSDML file

Why this topic is coming up right now

The issue is rarely the bus system itself, but rather the control system behind it. A large portion of the PROFIBUS networks in German industry are connected to a SIMATIC S7-300 or S7-400. Siemens has discontinued the S7-300, so the supply of replacement parts is only guaranteed for a limited time. Even today, some CPUs and communication modules on the used market cost significantly more than they did when new.

At the same time, expertise is dwindling. The colleagues who originally commissioned the system are gradually retiring. Younger technicians are learning TIA Portal and PROFINET, not STEP 7 Classic and troubleshooting with the bus monitor.

Data requirements are also increasing. Anyone who wants to transfer machine status data to the MES, trace quality data, or connect equipment to the production IT system via OPC UA will quickly reach the limits of a pure PROFIBUS architecture. This does not automatically create an urgent need for action. However, it does create a need to plan equipment modernization before a failure forces the issue.

Employees at work in the TIA Portal

When an Upgrade Is Really Worth It

The switch is almost always most cost-effective when work is already being done on the system. If you’re planning to replace the control system with an S7-1500, a large part of the effort is required anyway: hardware configuration, software migration, and commissioning. The fieldbus conversion can be handled at the same time with a manageable amount of additional effort.

The same applies to expansions and retrofits. New stations, additional robots, or a camera system for quality inspection typically come equipped with PROFINET interfaces. Anyone who sticks with PROFIBUS at that point ends up installing network adapters that will have to be removed later.

Sometimes the impetus comes from outside. Automakers specify their own control standards in their specifications, and these rely on PROFINET and PROFIsafe. For suppliers and plant manufacturers, the transition is then less a question of “if” and more a question of “when.”

Then there are the systems that simply cost time. When sporadic bus errors repeatedly cause downtime and the cause must be painstakingly investigated each time, PROFINET’s improved diagnostics often pay for themselves faster than expected.

When Waiting Is the Better Decision

Not every PROFIBUS system needs to be retrofitted. If a machine is running stably, its end of life is foreseeable, and the critical spare parts are in stock, there is little reason to intervene. This is especially true if no expansions are planned and the system does not need to provide data to higher-level systems. The key is to make this decision deliberately. A brief assessment of spare parts and remaining service life will show whether the system can continue on this path.

Complete transition or partial migration

Once the decision to adopt PROFINET has been made, the next question arises: should the transition be done all at once or step by step? A complete migration results in the cleanest architecture and eliminates the need for interim solutions. However, it requires a sufficiently long downtime window and thorough preparation. A phased migration spreads the effort and risk over a longer period of time. In return, it requires well-thought-out network planning to ensure that both systems work together reliably.

Mixed Operation with Gateways and Couplers

Modern controllers such as the S7-1500 support both protocols. Using communication modules or network adapters—such as PROFIBUS-PROFINET gateways and couplers—existing PROFIBUS devices can continue to operate while the controller is already running on the PROFINET network. This is particularly worthwhile for drives, valve islands, or measuring devices that are still technically sound and are only scheduled to be replaced when they reach the end of their service life.

The trade-off: Every network transition is an additional component that must be configured, documented, and understood in the event of a fault. The diagnostics for PROFIBUS stations remain at the current level. Nevertheless, mixed operation has proven effective as a stopgap measure over the past few years.

Gradual Migration During Ongoing Production

In many plants, a system is only available during holidays, plant shutdowns, or scheduled maintenance shifts. The migration is then broken down into segments, each of which fits into such a window. As much work as possible is moved forward for this purpose: Software and hardware configuration are prepared offline, and control cabinets are pre-assembled and tested. With virtual commissioning, the new program can even be tested against a model of the system before a single cable is reconnected. A fallback plan is also firmly incorporated into the schedule in case something does not go as planned at the end of the window.

This is how a retrofit works in practice

The first step is to take stock of the system. Which controller is installed, which devices are connected to the bus, and which of them have a PROFINET interface? And how up-to-date are the schematics and software versions? With older systems, it’s not uncommon for the documentation to differ from reality. Clarifying these details before the project begins saves valuable hours during the downtime window.

This results in the new network concept, including topology, addressing, and segmentation. The electrical design team implements the changes in EPLAN, including new bills of materials and updated control cabinet layouts. At the same time, the PLC programming team migrates the existing program to TIA Portal. Especially for systems that have evolved over the years, this involves more than just an automatic conversion. Program blocks are reviewed, cleaned up, and adapted to current standards.

Safety technology involves more effort than is often expected. If the safety system is redesigned using PROFIsafe and an F-CPU, the safety functions must be re-evaluated, verified using SISTEMA, and approved—just as is required for any other change to machine safety. This is followed by installation, commissioning within the agreed-upon timeframe, and training for operating and maintenance personnel to ensure that your team actually makes use of the new diagnostics.

When all these steps are handled by a single team, there is no need for handoffs between planning, control cabinet construction, programming, and commissioning. And with them go the points where, as experience shows, the most information is lost during retrofits.

What PROFINET Brings to Existing Systems

Operators notice the difference most quickly in diagnostics after a retrofit. PROFINET reports errors down to the individual port level, displays topology and line status, and significantly shortens the time it takes to locate a faulty device. Less search time means less downtime.

Because PROFINET is based on Ethernet, process data, parameterization, and communication with higher-level systems all share the same infrastructure. This makes integration with MES or ERP systems, the transmission of quality data, and access via OPC UA significantly easier.

In the long run, the switch pays off with every expansion. New devices, robots, and camera systems come standard with a PROFINET interface and can be integrated without network gateways. Replacement parts will be available for the foreseeable future.

Common Pitfalls During Migration

Most problems arise during preparation, not during programming. Missing or outdated documentation tops the list. If you don’t realize until a shutdown that something different is installed in the control cabinet than what’s shown in the plan, you’ll waste exactly the time you’re already short on.

It also becomes difficult for participants without a PROFINET variant. Older drives, specialized devices, or measurement equipment cannot always be replaced on a one-to-one basis. In such cases, it must be determined early on whether a replacement, a gateway, or a temporary solution makes the most sense. The appropriate device description files for new components must also be included in the planning.

Cabling is often underestimated. The purple PROFIBUS cable cannot be reused for PROFINET, but the existing cable routes usually can. For systems built to an automaker’s standards, their specifications for software, electrical design, and interfaces must also be taken into account. And the acceptance testing of safety technology must be firmly scheduled. It cannot be done on the fly on the last day.

Experience from Retrofit Projects

HDAO Controls brings over 15 years of experience in automation technology to the table, and control system migrations have always been part of our expertise. Our team has migrated S5 controllers to S7 for automotive manufacturers and modernized entire test cells. At the same time, we implement large PROFINET networks for interlinked production lines, such as an automotive line with over 30 controllers and approximately 1,700 PROFINET devices. As a Siemens Solution Partner, we work in accordance with automotive manufacturers’ standards as well as our own proven in-house standards.

Whether it’s a retrofit of a single machine’s control system or the modernization of an interlinked production line, our process always begins with an on-site analysis of the existing system. When retrofitting machines, this allows us to reliably determine the scope of the project, the required downtime, and the most sensible migration steps before the first component is ordered.

Plan Before a Failure Forces Your Hand

Whether upgrading from PROFIBUS to PROFINET is worthwhile depends less on the bus system than on the condition and future of your plant. If a modernization is already on the horizon, now is the right time. If the plant is running stably and its end of life is foreseeable, waiting may be the right choice. To determine which scenario applies to your plant, we’ll conduct an on-site assessment of the control system, field level, and documentation together with your maintenance team.

What Operators Need to Know Before Switching from PROFIBUS to PROFINET

Can I continue to use PROFIBUS devices with a PROFINET controller?

Yes. An S7-1500 with a PROFIBUS interface or a PROFIBUS-PROFINET gateway will continue to connect existing DP devices. Whether this is worthwhile depends on the individual device: Devices with a long remaining service life and a guaranteed supply of replacement parts can remain in use. Devices that are due for replacement anyway should be replaced immediately with a PROFINET version.

Has PROFIBUS been discontinued?

No. The standard is still maintained by the user organization PROFIBUS & PROFINET International, and PROFIBUS components are available on the market. However, new device developments are focused on PROFINET. Individual controller families, such as the SIMATIC S7-300—to which many PROFIBUS networks are connected—have been discontinued.

What does the discontinuation of the S7-300 mean for my existing PROFIBUS network?

The discontinuation affects the controller, not the network. Since an S7-1500 can also control PROFIBUS devices, the controller replacement can be brought forward. The fieldbus conversion can then follow later, for example, with the next plant expansion. This way, the effort and downtime are spread out over two planned steps.

Does the entire cabling system need to be replaced during the conversion?

The bus cables in the sections being converted will be replaced with PROFINET cables, as the purple PROFIBUS cable is not suitable for this purpose. Cable trays, cable ducts, and cable glands can generally continue to be used. A copper cable run for PROFINET may be no longer than 100 meters; for greater distances, fiber-optic cables are used.

What network components does a PROFINET network require?

The foundation consists of industrial-grade Ethernet cables with RJ45 or M12 connectors. Many PROFINET devices already have a built-in two-port switch, allowing lines to be set up without additional hardware. Industrial switches are required for star and tree topologies. If the network is to operate as a ring with media redundancy, the components involved must support MRP.

How long will a system be down during the retrofit?

That depends on the size and condition of the system. Preparation has the greatest impact: The more testing, prefabrication, and virtual commissioning are done offline, the shorter the actual downtime will be. Those who plan early can take advantage of existing maintenance windows instead of scheduling additional downtime.

Can the existing PLC program be imported?

STEP 7 projects from an S7-300 can be transferred to the TIA Portal. However, adjustments are necessary for use on an S7-1500, such as changes to system functions and block access. Programs from the S5 environment are typically restructured because the programming methods and capabilities differ too greatly. The existing sequence logic remains the technical foundation.

How much does it cost to convert from PROFIBUS to PROFINET?

The costs depend on the number of devices, the scope of the controller replacement, the effort required for safety technology, and the condition of the existing documentation. The available downtime window also plays a role, as it determines how much must be manufactured and tested in advance. A thorough assessment of the system is the basis for a reliable quote.